Transformer Differential Protection: Relay Settings, Configuration, Calculations & Testing

Transformer differential protection is the most sensitive and selective form of protection available for transformers in modern electrical power systems. When properly designed and configured, differential relays can detect even minor faults within the transformer protection zone while remaining completely stable for faults occurring outside the zone.

In this technical guide we will discuss the principles of transformer differential protection, walk you through detailed relay setting calculations, explore discrimination techniques that distinguish inrush current from real faults, and provide practical testing procedures.

What Is Transformer Differential Protection?

Differential Protection Relay Schematic Drawing

Transformer differential protection is based on a fundamental principle: under normal operation or external fault conditions, the current entering a transformer approximately equals the current leaving it. If a large unbalance in current exists between the primary and secondary sides of a transformer, it indicates an internal fault that requires immediate disconnection.

The Basic Principle:

\(\text{Under Normal Conditions: } I_{\text{primary}} = I_{\text{secondary}} \times \frac{V_{\text{primary}}}{V_{\text{secondary}}}\)

During Internal Fault:

\(\text{Differential Current (I}_{\text{diff}}\text{) = } I_{\text{in}} – I_{\text{out}}\)

When a differential current exists, the relay operates and sends a trip signal to circuit breakers on both sides of the transformer, isolating it in less than one cycle, typically 40-100 milliseconds. This fast response minimizes fault damage, limits heat generation, and prevents oil decomposition.

Differential protection is selective because it only responds to faults within its defined protection zone (between the two current transformers). Faults occurring outside this zone even on the secondary side just beyond the CT do not produce sufficient differential current to trip the relay.

Why Differential Protection for Transformers?

Transformers, especially those rated 10 MVA and above, require fast, sensitive primary protection. Differential protection offers several critical advantages:

  1. High Sensitivity – Can detect faults as small as 0.2 pu (20% of rated current)
  2. Selectivity – Responds only to internal faults, ignoring external faults
  3. Speed – Clears faults in less than one cycle (20 milliseconds at 50 Hz)
  4. No Intentional Time Delay – Unlike overcurrent relays, differential operates instantaneously
  5. Backup for Buchholz Relay – Catches faults the Buchholz relay may miss
  6. Turn-to-Turn Fault Detection – Can detect winding-to-winding short circuits

Types of Transformer Faults Detected by Differential Protection

Fault TypeDetection TimeTypical Fault CurrentRelay Element Used
Phase-to-Phase Short CircuitInstantaneous (< 100 ms)5-50 pu87T (Restrained) or 87H (High Set)
Phase-to-Ground Short CircuitInstantaneous to 1 cycle1-20 pu87G (Ground Differential)
Turn-to-Turn Winding FaultDelayed (depends on severity)0.1-0.5 pu87 with high sensitivity
Core Faults/Circulating CurrentsSeveral cycles to minutes0.05-0.2 puDedicated turn-to-turn protection
Bushing FlashoverInstantaneous3-15 pu87H (High Set)
Winding Insulation BreakdownInstantaneous to 1 cycle3-30 pu87T + 87H
Lead Connection FailuresInstantaneous1-5 pu87T
Tap Changer FaultsDelayed0.2-1 pu87T/87G

Percentage Biased Differential Relay: Operating Principle

The most widely used differential relay configuration is the percentage biased (or percentage restraint) differential relay. This relay compares the magnitude of differential current against a percentage of the through current (restraint or bias current).

Operating Characteristic Formula

The percentage biased relay operates according to:

\(\text{If } I_{\text{diff}} > I_{\text{pickup}} + K \times I_{\text{bias}}\)

\(\text{Then TRIP (where K is slope percentage in per unit)}\)

Where:

  • \((I_{\text{diff}})\) = Differential current (magnitude of current difference)
  • \((I_{\text{pickup}})\) = Minimum pickup setting (typically 0.2-0.3 pu)
  • \((I_{\text{bias}})\) = Bias current = Average of currents entering and leaving the zone
  • \((K)\) = Slope percentage (typically 15-30% for first slope)

Dual-Slope Operating Characteristic

Differential Relay Slope Characteristics

Modern differential relays use a dual-slope characteristic to provide both high sensitivity and high stability:

  • Slope 1 (Low Current Region): Steep slope (15-30%) for high sensitivity during internal faults with low through-fault currents.
  • Slope 2 (High Current Region): Shallow slope (100-200%) for high stability during external faults with high through-fault currents.

The transition between slopes typically occurs at 3-6 times rated current.

Calculating Differential Relay Settings: Practical Example

Let’s work through a complete example showing how to calculate settings for a real transformer:

Given Data:

  • Transformer: 315 MVA, 220 kV/110 kV, Delta-Wye connected
  • Primary CT: 800:5 (CTR = 160)
  • Secondary CT: 1200:5 (CTR = 240)
  • Transformer Impedance: 10%
  • Exciting Current: 0.5%

Step 1: Calculate Full Load Currents

Primary Full Load Current: \((I_1 = \frac{315 \times 1000}{\sqrt{3} \times 220} = 826.66 \text{ A})\)

Secondary Full Load Current: \((I_2 = \frac{315 \times 1000}{\sqrt{3} \times 110} = 1653.32 \text{ A})\)

Step 2: Calculate CT Secondary Currents

Primary CT Secondary: \((I_{1,\text{ct}} = \frac{826.66}{160} = 5.17 \text{ A})\)

Secondary CT Secondary: \((I_{2,\text{ct}} = \frac{1653.32}{240} = 6.89 \text{ A})\)

Step 3: Calculate Pickup Setting

The pickup setting should be above the exciting current (0.5% of primary FLC):

Exciting Current: \((I_{\text{ex}} = 0.5\% \times \frac{826.66}{160} = 0.026 \text{ A (CT secondary)})\)

Recommended Pickup: 20% of primary FLC = \((\frac{20\% \times 826.66}{160} = 1.033 \text{ A})\)

This provides approximately 40:1 margin above exciting current—sufficient for stable operation.

Step 4: Calculate Slope Setting

Error Sources (Worst Case):

  • CT Ratio Error: ±1.5%
  • Tap Variation: ±10%
  • Relay Accuracy: ±2%
  • Safety Margin: 10%

Total Error = 1.5 + 10 + 2 + 10 = 23.5%

Required Slope ≥ 25% (rounded up to nearest standard value)

Discriminating Between Inrush Current and Internal Faults

One of the greatest challenges in transformer differential protection is distinguishing between magnetizing inrush current (which should NOT trip the relay) and internal fault current (which MUST trip the relay immediately).

CharacteristicMagnetizing InrushInternal Fault Current
Duration0.1-1.0 secondsContinuous until cleared
Magnitude TrendDecays exponentiallyConstant or increasing
Waveform ShapeHighly distorted, peakySinusoidal or slightly distorted
2nd Harmonic Content30-70% of fundamental< 20% of fundamental
5th Harmonic Content10-30% of fundamental< 15% of fundamental
DC ComponentStrong (decreases with time)Minimal or absent
Appears on Both SidesOnly on energized side (initial)Yes (appears on both sides)
SymmetryAsymmetrical, unidirectional peaksSymmetrical, bidirectional
Detection MethodHarmonic restraint/blockingBiased differential slope
Typical Relay ResponseBlocked/Restrained (no trip)Trip (instantaneous or delayed)

Harmonic Restraint and Blocking Methods

1. Second Harmonic Restraint

The most common discrimination technique. High 2nd harmonic content (present in inrush) causes the relay to raise its pickup threshold or reduce its sensitivity. The relay continuously monitors the ratio of 2nd harmonic to fundamental:

\(\text{Harmonic Ratio} = \frac{I_{\text{2nd harmonic}}}{I_{\text{fundamental}}} \times 100\%\)

If this ratio exceeds a threshold (typically 15-30%), the pickup is increased or operation is delayed, allowing inrush current to pass without tripping while still catching internal faults.

2. Second Harmonic Blocking

An alternative method where a separate blocking relay is activated by the 2nd harmonic component. Its contacts are in series with the differential relay operating coil, blocking trip during inrush events.

3. Fifth Harmonic Blocking

Used to prevent trips during transformer overexcitation (V/Hz overstress). When the 5th harmonic content exceeds a threshold (typically 25-40%), operation is blocked.

Current Transformer Saturation and Its Effects

Current transformer saturation is a critical phenomenon that affects differential relay operation, particularly during external faults with high primary currents. When a CT saturates, its secondary current becomes distorted and nonlinear, potentially causing false differential currents.

CT ParameterImpact on DifferentialMitigation
Ratio Error (±0.1-3%)Creates false differential currentUse matching CTs, slope ≥ 25%
SaturationUnequal saturation causes differential during external faultsHigh saturation voltage CTs, harmonic restraint
Remanent Flux (50-80% rated)Increases saturation for subsequent faultsControlled de-energization, demagnetization
Phase Angle Error (0-30 min)Vector addition errorsNumerical relay compensation
DC OffsetDistorted secondary waveformRelay filters DC component automatically

Transient Bias Technique: Modern numerical relays use an advanced algorithm that temporarily increases the operating threshold when CT saturation is detected. This provides high stability during external faults while maintaining fast tripping for true internal faults, even in the presence of harmonics from CT saturation.

High Set Element: Unrestrained Differential Protection

In addition to the biased differential element (87T), modern relays include an unrestrained high-set element (87H) that provides instantaneous tripping for severe internal faults:

High Set Pickup: Typically 8-15 pu of rated current, set above the maximum possible inrush current but below the lowest internal fault magnitude.

Time Delay: Usually 0.5-1.5 cycles to avoid nuisance tripping during inrush.

Purpose: Ensures fast tripping (< 1 cycle) for high-magnitude internal faults even if the biased element is restrained by harmonics from CT saturation.

Ground Differential Protection (87G)

In addition to phase differential protection, transformers with accessible neutral connections may have ground differential protection (87G) that specifically monitors zero-sequence (ground) currents. This element:

  • Detects phase-to-ground faults inside the transformer
  • Provides additional sensitivity for winding-to-ground insulation faults
  • Operates independently of phase balance conditions
  • Uses similar percentage-biased characteristics as phase differential

Relay Setting Parameters and Typical Values

Setting ParameterTypical RangePurpose
Pickup (87T – Restrained)0.2-0.3 pu (20-30%)Covers excitation current, CT errors, tap variation
Slope 1 Percentage15-30%Fast tripping for low through-fault currents
Slope 2 Breakpoint3-6 pu of FLCTransition to second slope
Slope 2 Percentage100-200%Stability for high external fault currents
High Set Pickup (87H)8-15 puInstantaneous tripping for severe internal faults
High Set Time Delay0.5-1.5 cyclesPrevents nuisance trip during inrush
2nd Harmonic Restraint15-30% of fundamentalBlocks operation during magnetizing inrush
5th Harmonic Threshold25-40% of fundamentalBlocks operation during overexcitation
CT Ratio CorrectionAutomaticAccounts for different CT ratios on HV/LV
Vector Group CompensationDelta/Wye configuredAligns currents based on transformer connection

Common Misoperation Causes and Solutions

IssueCauseSolution
False Trip on Transformer InrushHigh 2nd harmonic in inrush currentEnable 2nd harmonic blocking/restraint (15-30%)
Failure to Trip on FaultOver-sensitive pickup settingReduce pickup setting or lower slope
Nuisance Trip on External FaultSlope too steep, CT errors underestimatedIncrease slope percentage, verify CT errors
Trip on Tap Changer OperationLarge differential current from tap changeCoordinate with tap changer control
Trip During OverexcitationHigh 5th harmonic during V/Hz overstressEnable 5th harmonic blocking (25-40%)
Trip During CT SaturationDifferent saturation on HV and LV sidesUse CT saturation detection, increase 2nd harmonic threshold
Unequal CT RatiosDifferential current even at no loadUse internal matching CTs or adjust relay settings
Vector Group MismatchPhase shift not accounted forConfigure relay for delta/wye connection compensation

Numerical vs. Electromechanical Relays

While this technical guide focuses on modern numerical (microprocessor-based) differential relays, it’s important to understand the advantages:

Numerical Relay Advantages:

  • Automatic CT ratio correction without external matching CTs
  • Sophisticated harmonic analysis for better inrush discrimination
  • Programmable operating characteristics
  • Self-diagnostic and self-supervision functions
  • Event recording and data storage
  • Easy settings modification
  • Better accuracy and repeatability

Numerical Relay Setting Steps:

  1. Enter transformer nameplate data (kVA, voltages, vector group)
  2. Enter CT data (CTR on HV and LV sides)
  3. Relay automatically calculates vector compensation
  4. Enter pickup and slope settings (or use defaults)
  5. Enable harmonic blocking/restraint features
  6. Commission and test per procedure

Commissioning and Testing Transformer Differential Relays

Proper relay commissioning ensures reliable protection. The following tests must be performed:

Test ItemProcedurePass Criteria
Relay Settings VerificationVerify all settings match design calculationsAll settings correctly entered
Stability Test (No Load)Inject rated current both sides with same polarityRelay remains stable (no trip)
Pickup TestInject differential current above pickup on one sideRelay trips instantaneously
Slope TestInject currents to plot relay operating characteristicOperating points match design within ±10%
High Set TestInject unrestrained current above high set pickupRelay trips as designed
Harmonic Restraint Test (2nd)Inject fundamental + 2nd harmonic at threshold levelRelay blocks/restrains when 2nd harmonic exceeds threshold
Harmonic Blocking Test (5th)Inject fundamental + 5th harmonic at threshold levelRelay blocks when 5th harmonic exceeds threshold
CT Saturation Detection TestSimulate CT saturation condition with external faultRelay remains stable during external fault
Inrush Current Immunity TestApply recorded inrush waveform to relay inputsRelay does not trip during inrush event
Phase Rotation TestVerify correct trip for each phase combinationCorrect phase current measured for each phase

Testing Equipment: Modern relay testing requires automated test sets such as Omicron, Doble, Schweitzer, or equivalent equipment to inject precise three-phase currents and voltages and verify relay operation.

Best Practices for Transformer Differential Protection

Setting Design

  1. Perform CT error calculations for both nominal tap and maximum tap positions
  2. Apply safety margins (typically 10-20%) for all settings
  3. Coordinate with backup protection (overcurrent relays)
  4. Document all calculations and design decisions
  5. Use standard setting templates for consistency

Installation and Configuration

  1. Ensure correct CT polarity and phasing
  2. Verify vector group compensation in relay programming
  3. Use properly sized and labeled wiring
  4. Maintain low CT secondary burden
  5. Properly ground and shield relay signal cables

Maintenance and Monitoring

  1. Perform periodic relay functional tests (every 3-5 years)
  2. Review event records for potential issues
  3. Monitor relay diagnostics and alarms
  4. Update settings if transformer parameters change
  5. Train personnel on relay operation and testing

Differential Protection for Three-Winding Transformers

Three-winding transformers require an additional restraint winding for the tertiary connection. The operating criterion becomes:

\(\text{If } I_{\text{diff}} > I_{\text{pickup}} + K \times (I_{\text{bias1}} + I_{\text{bias2}} + I_{\text{bias3}})\)

Modern numerical relays handle this automatically through software configuration.

Conclusion

Transformer differential protection represents the fastest and most selective form of primary protection available for large power transformers. By understanding the fundamental principles of percentage biased differential relays, properly calculating pickup and slope settings, and implementing fault discrimination techniques, you can ensure your transformers are protected against internal faults while maintaining stability for external faults and transient conditions.

Key Takeaways:

  1. Differential protection detects current imbalance between transformer primary and secondary sides
  2. Percentage biased characteristic provides both sensitivity and stability through dual slopes
  3. Harmonic restraint/blocking discriminates inrush from internal faults with 99%+ reliability
  4. Proper settings require calculation based on CT errors, tap variation, and transformer impedance
  5. Numerical relays provide advanced features including CT saturation detection and transient bias
  6. Comprehensive testing is essential for reliable operation during actual fault events
  7. Coordination with backup protection ensures selective clearing of faults

Leave a Comment

Your email address will not be published. Required fields are marked *

Scroll to Top